Have you ever bothered about installing a heat meter? After purchasing the product, relevant people need to install it skillfully, so the following key points should be ignored. Let's take a quick look.
Installation of heat meter flow sensor: Generally, the heat meter can be installed at the water supply end the water return end when leaving the factory. the corresponding pipe for installation. During installation, it is required to install according to the direction of the water flow indicator arrow on the flow meter pipe section, it is recommended to install the shutoff valve before after the flow sensor for easy maintenance. When installing the heat meter, try to avoid the pipeline the liquid flows downward ( diagonally downward) to prevent the liquid filling the pipeline. During installation, do the commanding point of the pipeline to prevent inaccurate measurement due to bubbles in the pipeline. The two transducers of the flowmeter shall be on the same horizontal plane, otherwise the two transducers installed at high low levels may be inaccurate measured due to the convergence of air.
Heat meter
The flow sensor of the heat meter shall be installed on the pipe with a diameter equal to its nominal diameter (generally, the straight pipe section with a diameter of more than 10 times the nominal diameter is at the front of the meter, the straight pipe section with a diameter of more than 5 times the nominal diameter is at the back of the meter. There shall be no other temperature measuring, pressure measuring, filter, valve other elements within the straight pipe section). The distance between flowmeter electromagnetic interference source, such as switch, control, water pump other equipment shall be at least 1 meter. The conductor spacing shall be at least 0.2m. If the position reserved for the meter body is too large the unevenness of the flange is at an angle with the flange of the meter body when the flange is installed on the pipe, do tighten the bolt forcibly at this time, otherwise it is likely to cause the meter body to break. The correct method should be to remove the unreasonable flange reinstall it.
The above are the installation points of the flow sensor of the heat meter. I hope it can help you. In addition, I suggest you seek the advice of relevant people before purchasing the product.